Select Page

SODIUM HYPOCHLORITE DISINFECTION – FLOW PACED

MAK Water’s Sodium Hypochlorite Disinfection Flow (SHDF) plants are designed to automatically maintain the correct amount of free chlorine in an existing reticulation line, in accordance with Australian Drinking Water Guidelines (ADWG). The standard treatment process includes an inline chlorine analyser which monitors residual free chlorine and a dosing pump to automatically dose liquid sodium hypochlorite as required, into the potable or treated water pipeline.

Categories: ,

Description

The system components are sized to suit the required chlorine usage rate and the sodium hypochlorite storage tank refill frequency. Options are provided for duty standby dosing pumps to improve plant reliability, a flow transmitter, a static mixer if required to improve mixing. MAK Sodium Hypochlorite Disinfection Flow plants are available as either skid mounted for internal or external installations, or containerised with air conditioning to avoid chlorine degradation.

STANDARD SPECIFICATIONS

Parameter Units SHSF-60 SHSF-100 SHSF-200 SHSF-500 SHSF-1000 SHSF-2500 SHSF-5000
Sodium Hypochlorite  Storage Tank Size L 60 100 200 500 1,000 2,500 5,000
Free Chlorine Residual (target) mg/L 0.2 ~ 2 (as per Australian Drinking Water Guidelines ADWG)
Raw Water Temperature °C 15 ~ 35
Ambient Design Temperature °C 5 ~ 35 (15 ~ 30 for insulated containerised system)
Raw Water Flow Rate m³/hr 0 ~ 1,000
Raw Water Pressure kPa 0 ~ 800
Power Supply AC 240V, 1 phase, 50Hz or AC 415V, 3 phase, 50 Hz
Power Consumption (approx.) kW 0.5
Container Size (optional) ft 1 x 10’ 1 x 10’ 1 x 10’ 1 x 10’ 1 x 10’ 1 x 20’ 1 x 20’

STANDARD INCLUSIONS + OPTIONS

✓= Standard Supply o = Optional Supply – = Not Applicable

Equipment SHSF-60 SHSF-100 SHSF-200 SHSF-500 SHSF-1000 SHSF-2500 SHSF-5000
Skid Mounted Plant
Sodium Hypochlorite Dosing Pump
Bunded Sodium Hypochlorite Storage Tank
Chlorine Analyser
Control System
Alarm Signal Output for Client Interface
Containerised Plant c/w A/C & Lights o o o o o o o
Container Non-slip Floor Coating o o
Container Insulation (walls & ceiling) o o o o o o o
Container Side Access Door o o
Duty Standby Dosing Pumps o o o o o o o
Flow Transmitter (existing reticulation line) o o o o o o o
Static Mixer o o o o o o o
Safety Shower & Eyewash Station o o o o o o o
Solar Power System o o o o o o o
Premium Instrumentation Package o o o o o o o

 

Instrumentation Standard Package Premium Package
Pressure Switch (existing reticulation line)
Float Switch (sodium hypochlorite storage tank)
Chlorine Analyser (4-20mA)
Level Transmitter (4-20 mA, sodium hypochlorite storage tank)
Data Logger (residual chlorine)
Remote Monitoring & Control Capabilities


DISCLAIMER:
 MAK Water is continuously updating and improving its products and services, so please contact us for more detailed information or to confirm specifications. MAK Water takes no responsibility for any errors resulting from the use of information contained within this document.